JANUS – Status display

Emitter – JANUS ML / MT

1 Red LED2 Green LED3 Yellow LEDMeaning
System power-on – Initial TEST for 5 seconds
Test conditon
GUARD condition
FAIL condition. See next « fail condition table »

Fail condition

1 Red LED2 Green LED3 Yellow LEDMeaning
BlinkingInternal fault
BlinkingBlinking
BlinkingBlinking

Emitter – JANUS MI / J / J LR

1 Red LED2 Green LED3 Yellow LED4 RANGEMeaning
System power-on – Initial TEST for 5 seconds
Test conditon
GUARD condition
High range selected
FAIL condition. See next « fail condition table »

Fail condition

1 Red LED2 Green LED3 Yellow LED

4 RANGE

Meaning
BlinkingInternal fault
BlinkingBlinking
BlinkingBlinking
BlinkingBlinkingCorrect the range selection on the Emitter Unit

Receiver – JANUS MI / ML / MT and ACTIVE ELEMENT JANUS MI TRX / ML TRX / MT TRX

1 Red LED2 Green LED3 Orange LED4 Clear/Override LEDS1 LEDS2 LEDS3 LEDS4 LEDMUT LEDC DisplayMeaning
   8System power-on – Initial TEST for 5 seconds

In the next 10 seconds, the display and the leds will show the configuration selected

LEDStatusMeaning
S1Enabling of timeout 30 s.
S1Enabling of timeout 90 min.
S2With 4 sensors, enabling of sequential Muting
S2With 4 sensors, enabling of concurrent operation mode
S3Manual restart functioning mode enabled
S3Automatic restart functioning mode enabled
S4External relays feedback control enabled
S4External relays feedback control disabled
MUTMuting configuration with 4 sensors
MUTMuting configuration with 2 sensors
1 Red LEDOSSD outputs set to OFF
4 Clear/OverrideAutomatic override with pulse command
4 Clear/Override Manual overrun action with hold to run
DisplayCConfiguration

During the normal functioning

LEDStatusMeaning
S1Interruption Sensor 1
S1Sensor 1 clear
S2Interruption Sensor 2
S2Sensor 2 clear
S3Interruption Sensor 3
S3Sensor 3 clear
S4Interruption Sensor 4
S4Sensor 4 clear
MUTMuting active
MUTLight curtain active – GUARD condition
1 Red LEDOSSD outputs set to OFF
2 Green LEDGUARD condition
3 Orange LEDWeak signal
4 Clear/OverrideLight curtain in override, OSSD outputs set ON. « o » letter appears on the display and at the same time the external Muting/Override lamp blinks.
4 Clear/Override BlinkingOverride request
DisplayDuring normal functioning
F – CodeFault detected. Displayed alternatively to the error code. See next « Fail condition Table »

Fail condition

Configuration errors

  • C: Incorrect configuration of the system (the flashing led together with the C indicates the incorrect type of configuration). See Technical manual 
  • L: Muting light not present or fault
  • U: Incorrect « SYSTEM STATUS » or overload signal connection
  • E: External contact enabling/disabling signal missing or contactors feedback missing
  • II: Unstable Muting sensors signals or Barrier configured for 2 sensors but found 3 or 4 sensors (the corrispondent led flashes)

Faults

  • 3: Internal error 
  • 4: Internal error 
  • 5: Internal error on the OSSD outputs (or incorrect connection of these)
  • 6: Shortcircuit between the OSSD outputs
  • A: Internal error
  • 0: Overload of the OSSD outputs
  • 1: Interfering Emitter detected (The code remains visibile for at least 30s)
  • t: Override with pulse command expired

Receiver – JANUS J / J TRX / J TRX

1 Red LED2 Green LED3 Orange LED4 Clear/Override LEDMAN/AUTO LEDEN EDM LEDC DisplayMeaning
 8System power-on – Initial TEST for 5 seconds

In the next 10 seconds, the display and the leds will show the configuration selected

LEDStatusMeaning
MAN/AUTO LEDManual restart functioning mode enabled
MAN/AUTO LEDAutomatic restart functioning mode enabled
EN EDM LEDExternal relays feedback control enabled
EN EDM LEDExternal relays feedback control disabled
1 Red LEDOSSD outputs set to OFF
DisplayCConfiguration

During the normal functioning

 

LED

StatusMeaning
1 Red LEDOSSD outputs set to OFF
2 Green LEDGUARD condition
3 Orange LEDWeak signal
4 Yellow LEDLight curtain clear, OSSD outputs set OFF (the receiver is waiting for a Restart signal)
DisplayNormal functioning
F – CODEFault detected. Displayed alternatively to the error code. See next « Fail condition Table »

Fail condition

Configuration errors

  • C: Incorrect configuration of the system (the flashing led together with the C indicates the incorrect type of configuration). See Technical manual 
  • E: External contact enabling/disabling signal missing or contactors feedback missing

Faults

  • 0: Overload of the OSSD outputs
  • 1: Interfering Emitter detected (The code remains visibile for at least 30s)
  • 2: Outputs OSSD incorrectly connected to +24VDC
  • 3: Internal error 
  • 4: Internal error 
  • 5: Internal error on the OSSD outputs (or incorrect connection of these)
  • 6: Short circuit between the outputs OSSD
  • A: Internal error